Cat C32 Generator Set (US EPA Tier 3 / IMO II)

Cat C32 Generator Set (US EPA Tier 3 / IMO II)

Cat C32 Generator Set (US EPA Tier 3 / IMO II)

Generator Set Specifications
Minimum Rating
219 ekW
Maximum Rating
940 ekW
Frequency
60hz
Engine Specifications
Configuration
Vee-12, 4-stroke-Cycle-Diesel
Aspiration
Turbocharged-aftercooled aspiration
Bore
5.71in
Stroke
6.38in
Displacement
1959in³
Emissions
U.S. EPA Tier 3 / IMO II emissions certified
Rated Engine Speed
1800 rpm
Governor
Electronic (A4 ECM)
Generator
SR5 - Form Wound
Refill Capacity
Lube Oil System w/ oil filter change: 146 L (38.5 gal)
Cooling
Heat exchanger, keel or radiator cooled
Oil Change Interval
750 hrs
Generator Set Dimensions
Length
167.2 in/4245 mm (minimum), 226.1 in/5742 mm (maximum)
Width
59.9 in/1521 mm (minimum), 89.8 in/2280 mm (maximum)
Height
70.4 in/1747 mm (minimum), 92.8 in/2356 mm (maximum)
Package Dry Weight
15721 lb/7131 kg (minimum), 21998 lb/9978 kg (maximum)

Standard Equipment:

Air Inlet System
  • Separate circuit aftercooled (SCAC)
 
Control System
  • 24V control system
 
Cooling System
  • Heat exchanger, keel or radiator cooled
  • Watercooled exhaust manifold and turbocharger
  • Hard seawater lines – no flexible hoses
  • Flanges for cooling connections, ANSI or DIN
 
Fuel System
  • Duplex fuel filters with hybrid fuel lines
  • Fuel transfer and priming pump
 
Generators And Generator Attachments
  • IP23, air cooled, form wound SR5 generator offered in 440, 480 and 690V
 
Lube System
  • Oil fill, simplex filter and dipstick
 
Mounting System
  • Helical spring/rubber isolated mounting for vibration and structure borne noise reduction
 
General
  • Right or left hand service sides
  • Customer wiring and service tool connector
 

Optional Equipment:

Air Inlet System
  • Closed crankcase ventilation
 
Alarm And Protection
  • MGCP II or MGCP IIIB control panel with Cat® alarm and protection system
  • IP44 generator protection
 
Exhaust System
  • Muffler
  • SOLAS approved spray shielding
 
Charging System
  • Charging alternator
 
Control System
  • EMCP 4.2 control panel
 
Fuel System
  • Installed primary fuel filter with water separator and manual or electric priming pump
  • Fuel cooler
 
Lube System
  • Duplex oil filters
 
Starting System
  • Starting motors – air, electric or dual
 

    This site is protected by reCAPTCHA and the Google Privacy Policy and Terms of Service apply.